The T-CDI-5400-20S is a flowmeter for compressed air systems. It measures flow by maintaining one probe warmer than the other. It calculates the mass velocity from the amount of heat required, and then calculates the flow on the basis of pipe area. This model fits 2" steel pipes.
Requires analog port selection during U30 system configuration and use of a S-FS-CVIA when using the H22-001 logger.
Features:
This adds the ability for users to be able to measure compressed air flow (SCFM). 
Easy to install 
Digital display 
 
Environment: Indoor 
Measurement: Compressed Air Flow
specification:
Measurement range, 5200 model: 1 - 80 SCFM 
Measurement range, 5400 model: 3 - 350 SCFM (calibrated), 350 - 600 (unclibeated) 
Accuracy: (5200 model) 5% of reading plus 1% of full scale @ air temperatures 40 - 1200F 
Accuracy: (5400 model calibrated range) 5% of reading plus 1% of full scale @ air temperatures 40 - 1200F; (5400 model extended range) 7% of reading from rated fule scale to 150% of calibrated range, @ air temperatues 40 - 1200F 
Medium: Compressed air, nitrogen 
Operating pressure, 5200 model: 30 to 170 psig for best accuracy. 200 psig max on Sch 40 steel 
Operating pressure, 5400 model: 200 psig max on Sch 40 steel 
Input power: 250 mA @ 18 - 24 VDC 
Output resistence: 400Ω max 
Response time: 1 sec to 63% of final value 
Output: selectable 4 - 20mA or pulse 
Display: 4-digit LED 
Ring material: Aluminum 
Size / Weight, 5200 model: 3.2x2.2x1.6 in / approx. 1.2 lb 
Size / Weight, 5400 model: 3.2x2.2x1.6 in / approx. 1.4 lb 
Note: Recommended: 5200-DG (and 5400-S-DG) Drill Guide that facilitates accurately locating the holes that are needed to mount the flowmeter.
Producing Area:USA