The F900-L-P Airflow Sensor is designed to measure the velocity of airflows in applications such as HVAC, industrial processes, automotive, air filtration systems, electronics enclosures and critical containment areas.
Requires analog port selection during U30 system configuration and use of a S-FS-CVIA when using the H22-001 logger. 
Features:
This adds the ability for users to be able to measure air velocity (in ducts, e.g.) from which CFM can be computed. 
 
Environment: Indoor 
Measurement: Air Velocity
specification:
Measurement ranges, "O" model:  0.15 - 5 m/s (30 - 985 fpm) 
Measurement range, "P" model:  0.15 - 10 m/s (30 - 1969 fpm) 
Accuracy:  Greater of 10% of reading or +/-0.05 m/s or 1% full-scale 
Standard medium:  Air at standard pressure (101.3 kPa, 29.95" Hg) 
Operating temperature range:  0 - 700C (32 - 1580F) 
Storage temperature:  -10 to 1000C 
Supply voltage:  7-13 VDC 
Supply current:  40 - 75 mA (10K ohm nominal) 
Warm-up time:  < 5 sec     
Response time:  1.5 sec 
Output:  Linear 0 - 4 VDC full scale for calibrated range, up to 4.9 VDC beyond calibrated range 
Sensor head material:  Plastic 
Dimensions:  100 mm x 12 mm diameter for "S" model, 91 mm x 12 mm for "L" model 
Weight:  "S" model 1 oz., "L" model 1.8 oz. 
Vibration:  Up to 25 G 
Acceptable angle:  +/- 300 from perpendicular 
Repeatability:  +/- 1% under same conditions
Producing Area:USA